Additional Resources
 
1)  MVAC performance testing and refrigerant charging:
 
 
 
2) ESCO 608 study guide.  Study Guide
 
3) Air handler schematic:   Schematic 
 
4) Condensing unit schematic:  Picture
 
5) Air handler control board:  Picture
 
6) Does the EPA REALLY go after individuals for violations?  Read this ...
 
I guess this means that if you plan to steal a condensing unit you better take your recovery equipment with you or you will face the Feds as well as local law enforcement!
 
 
7 CHECKING SMALL APPLIANCE RELAYS, OVERLOADS AND COMPRESSORS
 
The overload should have continuity.
If the appliance cycles on and off with a click, the compressor relay may be bad. Does it rattle when you shake it?
 
 
 
The formula for checking the resistance of the compressor windings:
S = Start
C = Common
R = Run
S & C +  R & C should equal S & R.  The second highest resistance is found between S & C.
 
Test the compressor for ground. See B below and the above page image for instructions.
 
 
 
 
8) CHECKING A REFRIGERATOR'S COLD CONTROL (THERMOSTAT)
 
 
 
9) The sequence of steps, in their proper order, for a gas fired furnace that uses a HSI ignition are:
10)  Pressure ⁄ Temperature Chart apps for your phone or tablet
11)  "Emerson Check & Charge" is an app that can be used to calculate superheat and subcool values. It can be downloaded from the App Store or Play Store.
 
12)  Checking a hot surface igniter (HSI)
 
     Silicone Nitride(Match stick shape)
          15 - 20 ohms
      Silicone Carbide ("M" shape)
           50 - 90 ohms
 
The following silicone carbide HSI is bad.  Why?
 
 
 
 